Interactive calculator
CT & VT Sizing
Instrument-transformer ratios and burden screening, CT and VT tabs.
Before you calculate
Learn more — complete guide →Instrument-transformer ratio and burden screening
CT and VT tabs. A VA comparison never proves the accuracy class, the accuracy range or saturation performance.
Step 1
CT and its secondary circuit
Advanced: lead temperature and path, operating current, class, ALF (optional)
20 °C by default; warm leads have a higher resistance.
With a common return, earth faults see the loop (2 x).
From the CT test report; without it the effective ALF is not evaluated.
Step 2
CT results
Check before relying on this result
- The burden is a scalar sum of rated device VA and lead I²R: a screening, not an accuracy, accuracy-range or saturation check.
Burden at rated secondary current8.00 VA of 10 VA (80.0 %)Within entered nameplate VA burden (screening only)
Lead resistance and lead burden0.280 Ω · 7.00 VAMargin 2.00 VA
Nominal ratio20 : 1
Effective ALFALF not evaluatedNeeds the rated ALF and Rct.
Safety: never open-circuit a CT secondary while the primary carries current: dangerous voltages appear. Short it with the approved terminals and procedure. Qualified personnel only.
1. Lead resistance
Copper, ρ = 0.0175 Ω·mm²/m at 20 °C; two-wire loop.
2. Burden at rated secondary current
Lead I²R plus the rated VA of the connected devices: a scalar screening sum.
Calculations use full precision internally; the displayed numbers are rounded for readability.