Interactive calculator

CT & VT Sizing

Instrument-transformer ratios and burden screening, CT and VT tabs.

Before you calculate

Instrument-transformer ratio and burden screening

CT and VT tabs. A VA comparison never proves the accuracy class, the accuracy range or saturation performance.

Learn more — complete guide →
Step 1

CT and its secondary circuit

Advanced: lead temperature and path, operating current, class, ALF (optional)
20 °C by default; warm leads have a higher resistance.
With a common return, earth faults see the loop (2 x).
From the CT test report; without it the effective ALF is not evaluated.
Step 2

CT results

Check before relying on this result
  • The burden is a scalar sum of rated device VA and lead I²R: a screening, not an accuracy, accuracy-range or saturation check.
Burden at rated secondary current8.00 VA of 10 VA (80.0 %)Within entered nameplate VA burden (screening only)
Lead resistance and lead burden0.280 Ω · 7.00 VAMargin 2.00 VA
Nominal ratio20 : 1
Effective ALFALF not evaluatedNeeds the rated ALF and Rct.
Safety: never open-circuit a CT secondary while the primary carries current: dangerous voltages appear. Short it with the approved terminals and procedure. Qualified personnel only.

1. Lead resistance

Copper, ρ = 0.0175 Ω·mm²/m at 20 °C; two-wire loop.

Rleads=k ρ LAR_{leads}=\frac{k\,\rho\,L}{A}
Rleads=2×0.0175×202.5=0.28 ΩR_{leads}=\frac{2\times 0.0175\times 20}{2.5}=0.28\ \Omega

2. Burden at rated secondary current

Lead I²R plus the rated VA of the connected devices: a scalar screening sum.

Stotal≈Sdevices+Isn2RleadsS_{total}\approx S_{devices}+I_{sn}^2R_{leads}
Stotal≈1+52×0.28=8 VAS_{total}\approx 1+5^2\times 0.28=8\ \text{VA}

Calculations use full precision internally; the displayed numbers are rounded for readability.