Imagine a motor drawing electricity from the grid. Some of that electricity becomes useful work, while some circulates between the supply and magnetic fields. The cables and transformer must carry the total current — not just the part doing useful work.
That is why AC systems use three connected quantities: active power (P), reactive power (Q) and apparent power (S).
The three kinds of AC power — in plain English
For a simple sinusoidal AC circuit, it helps to picture three different questions:
Active power
kWHow much real work or heat is produced?
Reactive power
kvarHow much power moves back and forth with magnetic or electric fields?
Apparent power
kVAWhat total volt-ampere loading must the supply carry?
The three quantities are not added like ordinary numbers. In sinusoidal conditions, P and Q form perpendicular components of a triangle, and S is its hypotenuse.
P — Power that performs useful work
Active power (P) is the average rate at which electrical energy is converted into work, light, heat or other energy. It is measured in watts (W) or kilowatts (kW).
A resistive heater uses active power to make heat. A motor draws active electrical power and converts part of it into shaft power, with the rest lost as heat, friction and other losses.
Q — Power associated with energy storage
Reactive power (Q) is associated with energy temporarily stored and returned by magnetic and electric fields. Its unit is the volt-ampere reactive (var), usually expressed as kvar.
Motors, transformers and reactors need magnetic fields, so their currents typically lag the voltage (inductive behavior). Capacitors do the opposite: their current typically leads the voltage.
Reactive power is not simply “wasted electricity.” It is part of how AC fields operate; however, it can increase current and loading without increasing useful kW. For a given active power, reducing unnecessary reactive power can reduce current.
S — What the supply must be able to carry
Apparent power (S) combines the voltage and the total RMS current. It is measured in VA or kVA. Transformers and many generators have kVA ratings because their electrical loading depends strongly on voltage and current.
For example, a load may do 8 kW of real work while requiring 10 kVA from the supply. The difference comes from its power factor, not from an extra 2 kW of energy consumption.
How P, Q and S fit together
Imagine P drawn horizontally and positive inductive Q drawn vertically. S completes the triangle. The angle φ (phi) is the angle between the P axis and S in this diagram.
This triangle is especially useful when you know two powers and need to calculate the third. For capacitive loads, signed Q is below the horizontal axis; the same magnitude relationship still holds.
Why voltage and current are not always in phase
Alternating voltage and current rise and fall continuously. With a pure resistor, they rise and fall together. With inductors and capacitors, one waveform shifts in time relative to the other. That shift is called the phase angle φ.
A phasor diagram represents sinusoidal voltage and current as arrows. Their angular separation shows φ; a waveform diagram shows the same relationship across time.
Explore the phase angle
Choose a type of load to see how current moves relative to the voltage reference.
A lagging current reaches its positive peak later than voltage. A leading current reaches it earlier. The diagrams use voltage as the 0° reference and assume sinusoidal steady-state conditions.
What does cos φ actually tell us?
For sinusoidal voltage and current, power factor describes how much of the apparent power becomes active power. A power factor of 1 means P and S are equal in magnitude; the current is in phase with voltage.
Suppose the electrical active power stays at 10 kW. At PF = 1, the apparent power is 10 kVA. At PF = 0.8, it becomes 12.5 kVA — so, at a fixed voltage, the supply current is 25% higher.
Single-phase vs. three-phase calculations
In a typical European 230/400 V system, one phase to neutral is nominally 230 V (L-N). Between two different phases it is nominally 400 V (L-L). These are different voltages, so the calculator changes both the label and its default value when you change the system.
Single-phase AC
Use the voltage between line and neutral for a standard line-to-neutral load:
Balanced three-phase AC
Use line-to-line voltage and line current for the total three-phase power:
The √3 factor comes from the 120° separation between phases in a balanced three-phase supply. It is not a correction factor for cable losses or efficiency.
Power factor is not the same as efficiency
This is one of the most common misunderstandings. Efficiency (η) compares useful mechanical output power with electrical active input power. Power factor compares electrical active input power with apparent power.
For a motor marked 11 kW on its shaft-output rating, you first account for efficiency to find the electrical active input. Then use power factor to find kVA and current.
What does HP on a motor nameplate mean?
HP (horsepower) on many motor nameplates means rated mechanical output power at the shaft. It is not the electrical power drawn from the supply. KiloVolt uses mechanical (imperial) horsepower, with the conversion shown below.
For instance, a 10 HP motor operating at 90% efficiency delivers approximately 7.46 kW at the shaft and draws approximately 8.29 kW of electrical active power at its rated condition. Power factor is then used to calculate apparent power and current.
Let's calculate two real-world examples
11 kW motor, 400 V, PF 0.85, efficiency 90%
The 11 kW is mechanical shaft output, so electrical input power is higher.
Displayed intermediate values are rounded. The final values are based on unrounded inputs.
2 kW electrical load, 230 V, PF 0.90
Here the 2 kW is already the electrical input, so no efficiency adjustment is needed.
Common mistakes to avoid
They are only numerically equal when power factor equals 1 under the stated assumptions.
Use the correct line-to-line or line-to-neutral voltage and the corresponding equation.
Efficiency only converts between useful output and active electrical input.
Inductive and capacitive systems can have opposite reactive-power signs. This calculator shows magnitude.
Actual cable and protection selection also requires installation conditions, temperature, voltage drop, fault levels, disconnection checks and applicable standards.
Now try it with your own numbers
Switch between single-phase and three-phase, adjust the power factor and view every calculation step with real values.
Open KiloVolt power calculator →