Engineering guide

Surge Protective Devices (SPDs) Explained

What an SPD does, what Type 1, 2 and 3 mean, how to read Uc, Up, In and Iimp, where to fit them and the installation rules that decide whether they work.

KiloVolt engineering toolkit

A surge lasts microseconds and can destroy electronics

A surge protective device (SPD) limits the short, high voltage that lightning and switching can put on a power line, and leads the surge current to earth. It is chosen by a few numbers on its label and it works only if it is fitted correctly, close to what it protects and with very short connections. This guide explains what an SPD does, what Type 1, 2 and 3 mean, how to read the label, how much the equipment withstands, where to fit SPDs in an installation and the rules that decide whether they work. The lightning protection guide covers how a strike produces the surge.

This is educational material. The requirements that apply to an installation come from the standards and national rules in force and from the manufacturer’s data. The typical values in this guide are examples, not a design.

Chapter 1

Where surges come from

A transient overvoltage is a rise of the voltage that lasts only microseconds. It comes from lightning, either a direct strike on the building or a strike near it that couples into the cables, and from switching in the network, for example when a large load is switched off. A 230 V circuit can see thousands of volts for a very short time.

Electronics are the most exposed. A single large surge can destroy a power supply at once, and repeated smaller surges can wear the components until they fail months later with no obvious cause.

Chapter 2

What an SPD does

An SPD is connected in parallel between the live conductors and earth. In normal operation it has a very high impedance and draws almost no current. When a surge raises the voltage above a threshold, it becomes conductive, leads the surge current to earth and limits the voltage across itself to the protection level Up. When the surge has passed, it returns to its high impedance. It is built with varistors, with spark gaps, or with both.

Each surge ages an SPD a little. A thermal disconnector inside takes it out of the circuit when it overheats at the end of its life, which is why most SPDs have a status indicator.

Chapter 3

Type 1, Type 2 and Type 3

The types come from IEC 61643-11 (EN 61643-11), which tests SPDs for low-voltage power systems with different test waves. They are also called test class I, II and III.

  • Type 1: tested with a 10/350 µs current wave, which carries a large part of the energy of a lightning current, and rated by its impulse current Iimp. It goes where part of the lightning current can enter the installation, for example in a building with an external lightning protection system.
  • Type 2: tested with an 8/20 µs current wave, the common surge in a distribution system, and rated by its nominal discharge current In and its maximum discharge current Imax. It is the usual SPD of a distribution board.
  • Type 3: tested with a combination wave, a 1.2/50 µs voltage wave with an 8/20 µs current wave, and rated by its open-circuit voltage Uoc. It is fitted close to the equipment as a complement to Type 1 or Type 2, not instead of them.

A combined Type 1+2 device does both jobs and is common at the origin of an installation.

Chapter 4

Reading the label

SymbolMeaning
UcMaximum continuous operating voltage: the highest voltage the SPD can stay connected to without conducting
UpVoltage protection level: the highest voltage that appears across the SPD while it diverts the surge
InNominal discharge current, 8/20 µs (Type 2)
ImaxMaximum discharge current, 8/20 µs: the largest single surge the SPD can take
IimpImpulse current, 10/350 µs (Type 1)
UocOpen-circuit voltage of the combination wave (Type 3)
IsccrShort-circuit current rating: the highest prospective short-circuit current the SPD with its backup protection can stand

Uc must be above the highest continuous voltage of the supply, otherwise the SPD would conduct in normal operation. For a connection between a phase conductor and neutral or earth in a 230/400 V TN or TT supply the usual rule is Uc of at least 1.1 × 230 = 253 V, which is why 275 V devices are common. Other connections and IT systems have their own values: follow the manufacturer’s table.

Chapter 5

How much the equipment withstands

Equipment is given a rated impulse withstand voltage Uw by its overvoltage category. For a 230/400 V installation the categories withstand 1.5, 2.5, 4 and 6 kV. The SPD must keep the voltage that reaches the equipment below the Uw of that equipment.

CategoryUw at 230/400 VTypical equipment
IV6 kVAt the origin: meters and main switchgear
III4 kVDistribution boards and fixed installation equipment
II2.5 kVAppliances and portable tools
I1.5 kVSensitive electronic equipment

The voltage at the equipment is the Up of the SPD plus the voltage that appears along its connecting conductors. A margin between Up and Uw is therefore needed, and a long connection can use up the whole of it.

Chapter 6

When an SPD is required

Whether an SPD is required depends on the national installation rules and on the date the installation was built. Where the rules require overvoltage protection, an SPD is part of the design; where they do not, it is a design choice, which is often worth making where electronics, communication equipment or photovoltaic inverters are involved. The conditions and the exceptions are in the rules that apply: this guide does not replace them.

A building with an external lightning protection system needs Type 1 SPDs at the origin of the installation, because part of the lightning current can enter through the incoming lines. Without such a system, a Type 2 SPD at the main board is the usual starting point.

Chapter 7

Where to fit SPDs

The first SPD goes at the origin of the installation, at the main board, where the surge enters. Further SPDs go at sub-boards and close to sensitive equipment. A surge that is limited at the origin can still be amplified in a long cable by oscillation, so the distance between the SPD and the equipment matters.

Where the SPDs goOrigin, sub-board and equipment, simplified
Surge from the supplyMain board (origin)SPDType 1 or Type 1+2Sub-boardSPDType 2EquipmentSPDType 3 or Type 2More than about 10 m of cable: add an SPD near the equipment
If the equipment is more than about 10 m of cable from the SPD, fit a second SPD near it

Older documents give 30 m instead of 10 m. Use the figure of the manufacturer and of the standard in force. Type 1 and Type 2 devices in series must also be coordinated, by a decoupling inductance or by enough cable between them, as the manufacturer states.

Chapter 8

Installation rules

  • Short connections: the total length of the conductors that connect the SPD to the live conductors and to the earth bar should be as short as possible, ideally about 0.5 m, because the voltage along them adds to Up.
  • No loops: route the conductors in a V shape to the SPD, with no loops, so that the connection does not add inductance.
  • Backup protection: fit the fuse or the circuit-breaker that the manufacturer specifies, so that a failed SPD does not leave a short circuit.
  • Connection by earthing system: the arrangement of the SPDs depends on the earthing system. In a TT supply a common arrangement has an extra SPD between the neutral and earth. Follow the manufacturer’s diagrams and see the earthing systems guide.
  • With an RCD: a surge current to earth can trip a residual current device. Fit the SPD upstream of the RCD, or use an RCD that tolerates surge currents, as the manufacturer states.
Short and long connectionsThe voltage along the leads adds to Up
Live lineSPDEarth barShort leads, about 0.5 m in total, no loopsLive lineSPDEarth barLong, looping leads add voltage and use up themargin
Chapter 9

End of life and special cases

An SPD that has done its job cannot be seen to be spent. Check the status window or the remote signalling contact regularly and after every storm, and replace a module whose indicator shows that it has reached the end of its life. A protected installation with a failed SPD is an unprotected one.

On the DC side of a photovoltaic system the SPDs must be rated for direct current, with a Uc chosen from the open-circuit voltage of the strings. The PV system guide covers the system design.

Chapter 10

Worked example

Choose. A 230/400 V TN-S board in a building without a lightning protection system. Uc: 1.1 × 230 = 253 V at least, so a 275 V device is chosen. Type: Type 2. As an example of typical values, In = 20 kA and Up = 1.5 kV.

Check. The equipment is category II with Uw = 2.5 kV. With 0.5 m of connecting conductors adding an illustrative 0.5 kV, the voltage at the equipment is about 1.5 + 0.5 = 2.0 kV, below 2.5 kV, so the simple voltage check is met. It does not prove protection: the surge duty, the earthing system and the installation still have to be checked.

Place. A machine is 25 m of cable from the board. That is more than 10 m, so a second SPD is fitted near the machine.