Engineering guide

IP Ratings Explained

How to read an IP code under IEC 60529: the solid-object and dust numeral, the water numeral, the letters, how to choose a rating and how to keep it.

KiloVolt engineering toolkit

How well does the enclosure keep things out?

The IP code tells how well an enclosure keeps out solid objects, dust and water, and how well it keeps people away from live parts. It is the first thing to check when a panel, a junction box or a luminaire goes into a dusty, wet or exposed place. This guide shows how to read the code, what each numeral was tested with, how to choose a rating and how to keep it after installation.

This is educational material. The requirements that apply to an installation come from the standards and national rules in force and from the manufacturer’s data.

Chapter 1

What an IP code is

The IP code (International Protection, also called Ingress Protection) is defined in IEC 60529, adopted in Europe as EN 60529. It describes the degrees of protection provided by an enclosure. It has the letters IP, a first numeral from 0 to 6 for solid objects and dust, a second numeral from 0 to 9 for water, and sometimes one or two letters. A numeral that is not specified is replaced by X.

Reading an IP codeIEC 60529, with an example
IP65BHInternational ProtectionSecond numeral, 0 to 9:waterSupplementary letter H,M, S or W (optional)First numeral, 0 to 6: solidobjects and dustAdditional letter A to D(optional): access tohazardous partsExample: IP65 is dust-tight and protected against water jets
Dashed boxes are optional. When a numeral is not specified it is replaced by the letter X, for example IPX4 for a rating on water only.
Each numeral is a separate claim that was tested separately: IP65 does not mean IP66 or IP67

The code applies to the enclosure as it was tested, with its own seals, covers and glands. It does not describe the explosion risk, corrosion, or the chemicals and the temperature the enclosure can stand. It is also not the same as the NEMA types used in North America.

Chapter 2

Solid objects and dust

The first numeral has two jobs. For levels 1 to 4 it says what size of object cannot get in and, at the same time, which part of a person cannot reach hazardous parts inside. The test uses a sphere of 50, 12.5, 2.5 or 1 mm, and for level 2 also a jointed test finger. Levels 5 and 6 are about dust. They are tested in a chamber with talcum powder.

First numeral: protection against solid objectsTest object sizes drawn to scale
IP1XObjects of 50 mmand largerBack of the handIP2XObjects of 12.5mm and largerFingerIP3XObjects of 2.5 mmand largerTools and thickwiresIP4XObjects of 1 mmand largerThin wires andsmall toolsIP5XDust-protectedSome dust mayenter, but notenough to do harmIP6XDust-tightNo dust enters
The first numeral says what the enclosure keeps out. A higher numeral includes the protection of the lower ones.
  • IP5X: dust-protected. Dust may enter, but not in an amount that harms the equipment or its safe operation.
  • IP6X: dust-tight. No dust enters, tested with a vacuum inside the enclosure. This is the level for very fine or conductive dust.
Chapter 3

Water

The second numeral rises from drips (1) to jets (5 and 6), immersion (7 and 8) and hot high-pressure jets (9). In every test the water must not enter in a quantity that harms the equipment or its safe operation.

Second numeral: protection against waterThe test conditions in short
IPX1Vertical dripsDrops falling straightdownIPX2Tilted dripsDrops with the enclosuretilted up to 15°IPX3Spraying waterSpray up to 60° from theverticalIPX4Splashing waterSplashes from anydirectionIPX5Water jets6.3 mm nozzle, 12.5l/min, from any directionIPX6Powerful water jets12.5 mm nozzle, 100 l/minIPX7Temporary immersionUp to 1 m deep for 30minutesIPX8Continuous immersionLonger or deeper, asagreed with the makerIPX9Hot high-pressure jetsAbout 80 °C and 80 to 100bar, from close range
The numerals 7 and 8 do not include the jet tests of 5 and 6. A device that meets both is marked with both, for example IP65/IP67.

The numerals 7 and 8 do not imply protection against jets: an enclosure that stands immersion has not necessarily been tested with jets. Where both matter, the enclosure carries both marks, such as IP65/IP67. IPX9 means that the enclosure was tested with high-pressure, high-temperature water jets at close range under the conditions of the standard, as needed for equipment washed down in food plants. It is not a guarantee against real cleaning conditions, detergents or chemicals: check the manufacturer’s data for those.

Chapter 4

Letters and impact (IK)

  • Additional letter A, B, C or D: used when the protection of persons against hazardous parts is better than the first numeral says, or when only that protection is stated. A is the back of the hand, B the finger, C a 2.5 mm tool and D a 1 mm wire. IPXXB therefore means finger-safe, and the first numeral is not specified.
  • Supplementary letter H, M, S or W: H is high-voltage apparatus, M means that the water test was made with the moving parts running, S with them stopped, and W means that the enclosure suits stated weather conditions.
  • IK code: a separate code, in IEC 62262, for resistance to mechanical impact. IK07 is 2 J, IK08 is 5 J, IK09 is 10 J and IK10 is 20 J. It does not follow from the IP code.
Chapter 5

Choosing a rating

Choose from the place and from what happens there: dust, rain, hose cleaning, flooding, and who can touch the enclosure. For live parts the wiring rules (IEC 60364-4-41) require an enclosure of at least IPXXB or IP2X, and for the easily reached top surface IPXXD or IP4X. The table gives common starting points. The project specification and the product standard decide.

PlaceCommon starting pointReason
Indoor electrical room, dry and cleanIP2XFinger-safe against live parts
Indoor workshop or store with dustIP4X to IP54Wires and dust, some splashes
Outdoors, exposed to rainIP54 or IP55, IP65 where hosedDust, rain and jets
Washdown areas, such as food plantsIP66 or IP69Powerful or hot jets
Pits that can floodIP67 or IP68Immersion

Do not over-specify. A higher rating costs more and can trap heat and condensation. Panels that dissipate a lot of heat may need ventilation, and then the rating falls to the level of the vents unless a heat exchanger or a filter fan with a stated rating is used. busbar sizing guide.

Chapter 6

Keeping the rating

Where the rating is won or lostSection through a wall-mounted enclosure, simplified
Inside the enclosureDoor gasket, continuous andcompressedHinge and latches that pressthe door evenlyWallCableCable gland, sealed on thecableBlanking plug in theunused entryDrain or breather
The IP rating of an assembly is that of its weakest part. A gland, plug or drain with a lower rating, a damaged gasket or an extra hole lowers the rating of the whole enclosure.
  • Cable entries: use a gland rated for the same IP as the enclosure, matched to the diameter of the cable. Close every unused entry with a plug of the same rating.
  • Drilling: a hole that is cut in the field is a new opening. Seal it, or the rating is not the rating on the label.
  • Door and gasket: close all latches, keep the gasket clean and continuous, and replace it when it is hard, flat or cracked.
  • Position: mount the enclosure in the orientation of the test. Glands should point down, so that water runs away from the entry. Fit a drain or breather where condensation can form.
Chapter 7

Worked example

Reading codes. IP54 is a dust-protected enclosure (5) that withstands splashes from any direction (4). IPX4 says nothing about dust. IP66 is dust-tight and withstands powerful jets. IP65/IP67 is dust-tight and withstands both jets and temporary immersion.

Choosing. A feeder pillar stands outdoors in a dusty place, is cleaned with a hose and sits in a low spot where water can stand for a short time. Dust-tight, jets and temporary immersion are needed, so the choice is IP65/IP67, or IP66 together with IP67.

Keeping. The enclosure is IP66, but the installer fits a gland that is only IP54 in one entry. The assembly is then IP54, because the rating of the whole is that of its weakest part. Replacing the gland with a correctly installed IP66 one is a necessary step, but it does not restore IP66 automatically: the whole assembly, including the other entries, must be checked before IP66 is claimed.