How well does the enclosure keep things out?
The IP code tells how well an enclosure keeps out solid objects, dust and water, and how well it keeps people away from live parts. It is the first thing to check when a panel, a junction box or a luminaire goes into a dusty, wet or exposed place. This guide shows how to read the code, what each numeral was tested with, how to choose a rating and how to keep it after installation.
This is educational material. The requirements that apply to an installation come from the standards and national rules in force and from the manufacturer’s data.
What an IP code is
The IP code (International Protection, also called Ingress Protection) is defined in IEC 60529, adopted in Europe as EN 60529. It describes the degrees of protection provided by an enclosure. It has the letters IP, a first numeral from 0 to 6 for solid objects and dust, a second numeral from 0 to 9 for water, and sometimes one or two letters. A numeral that is not specified is replaced by X.
The code applies to the enclosure as it was tested, with its own seals, covers and glands. It does not describe the explosion risk, corrosion, or the chemicals and the temperature the enclosure can stand. It is also not the same as the NEMA types used in North America.
Solid objects and dust
The first numeral has two jobs. For levels 1 to 4 it says what size of object cannot get in and, at the same time, which part of a person cannot reach hazardous parts inside. The test uses a sphere of 50, 12.5, 2.5 or 1 mm, and for level 2 also a jointed test finger. Levels 5 and 6 are about dust. They are tested in a chamber with talcum powder.
- IP5X: dust-protected. Dust may enter, but not in an amount that harms the equipment or its safe operation.
- IP6X: dust-tight. No dust enters, tested with a vacuum inside the enclosure. This is the level for very fine or conductive dust.
Water
The second numeral rises from drips (1) to jets (5 and 6), immersion (7 and 8) and hot high-pressure jets (9). In every test the water must not enter in a quantity that harms the equipment or its safe operation.
The numerals 7 and 8 do not imply protection against jets: an enclosure that stands immersion has not necessarily been tested with jets. Where both matter, the enclosure carries both marks, such as IP65/IP67. IPX9 means that the enclosure was tested with high-pressure, high-temperature water jets at close range under the conditions of the standard, as needed for equipment washed down in food plants. It is not a guarantee against real cleaning conditions, detergents or chemicals: check the manufacturer’s data for those.
Letters and impact (IK)
- Additional letter A, B, C or D: used when the protection of persons against hazardous parts is better than the first numeral says, or when only that protection is stated. A is the back of the hand, B the finger, C a 2.5 mm tool and D a 1 mm wire. IPXXB therefore means finger-safe, and the first numeral is not specified.
- Supplementary letter H, M, S or W: H is high-voltage apparatus, M means that the water test was made with the moving parts running, S with them stopped, and W means that the enclosure suits stated weather conditions.
- IK code: a separate code, in IEC 62262, for resistance to mechanical impact. IK07 is 2 J, IK08 is 5 J, IK09 is 10 J and IK10 is 20 J. It does not follow from the IP code.
Choosing a rating
Choose from the place and from what happens there: dust, rain, hose cleaning, flooding, and who can touch the enclosure. For live parts the wiring rules (IEC 60364-4-41) require an enclosure of at least IPXXB or IP2X, and for the easily reached top surface IPXXD or IP4X. The table gives common starting points. The project specification and the product standard decide.
| Place | Common starting point | Reason |
|---|---|---|
| Indoor electrical room, dry and clean | IP2X | Finger-safe against live parts |
| Indoor workshop or store with dust | IP4X to IP54 | Wires and dust, some splashes |
| Outdoors, exposed to rain | IP54 or IP55, IP65 where hosed | Dust, rain and jets |
| Washdown areas, such as food plants | IP66 or IP69 | Powerful or hot jets |
| Pits that can flood | IP67 or IP68 | Immersion |
Do not over-specify. A higher rating costs more and can trap heat and condensation. Panels that dissipate a lot of heat may need ventilation, and then the rating falls to the level of the vents unless a heat exchanger or a filter fan with a stated rating is used. busbar sizing guide.
Keeping the rating
- Cable entries: use a gland rated for the same IP as the enclosure, matched to the diameter of the cable. Close every unused entry with a plug of the same rating.
- Drilling: a hole that is cut in the field is a new opening. Seal it, or the rating is not the rating on the label.
- Door and gasket: close all latches, keep the gasket clean and continuous, and replace it when it is hard, flat or cracked.
- Position: mount the enclosure in the orientation of the test. Glands should point down, so that water runs away from the entry. Fit a drain or breather where condensation can form.
Worked example
Reading codes. IP54 is a dust-protected enclosure (5) that withstands splashes from any direction (4). IPX4 says nothing about dust. IP66 is dust-tight and withstands powerful jets. IP65/IP67 is dust-tight and withstands both jets and temporary immersion.
Choosing. A feeder pillar stands outdoors in a dusty place, is cleaned with a hose and sits in a low spot where water can stand for a short time. Dust-tight, jets and temporary immersion are needed, so the choice is IP65/IP67, or IP66 together with IP67.
Keeping. The enclosure is IP66, but the installer fits a gland that is only IP54 in one entry. The assembly is then IP54, because the rating of the whole is that of its weakest part. Replacing the gland with a correctly installed IP66 one is a necessary step, but it does not restore IP66 automatically: the whole assembly, including the other entries, must be checked before IP66 is claimed.